Home About Us Products News Sales Network Contact Us
Latching Relay (8)
Shunt (11)
Current Transformer (45)
DC Immunity Alternating Current Transformer
Current location:Home > Products > Current Transformer > DC Immunity

Smart Technology

SMT601

Electrical Parameter

Model

Primary Current (A)

Secondary
Current
(mA)

Accuracy

Load Resistance

(Ω)

Temperature (℃)

Humidity (25℃)

Rated Current

Max Current

SMT601

5

60

2.5

0.1

10

-40~85

≤95%

Technical Specification
(1).Meet the requirement of IEC61558-2 and IEC62052-11, fitting to the single phase or multi-phase electronic meter under voltage of working frequency 50(60) Hz .
(2).AC-Error.

Accuracy

0.1

Rated Current Percentage

5

20

100

120

200

400

Imax

Ratio Error ±(%)

0.1

0.1

0.1

0.1

0.1

0.1

0.1

Phase Error (')

8

8

8

8

8

8

5

(3).DC-Error.
Measured by watt hour meter and DC Immunity testing device, at 60/√2A ,the error of electronic meter is between ±3.0%d(Double Core).See the test theory as following draft:


Electrical Performance Specification
(1).Frequency insulation strength
The primary winding to the secondary winding can undertake frequency AC 4000V and will not be penetrated for six SECs. long by 1mA creepage.
(2).Insulation Resistance
The primary winding to the secondary winding ≥1000MΩ  (DC500V)
(3).Leads requirements
The secondary winding leads are two UL1430#26 silica gel soft wires. One is red and the other is black. And filled by black epoxy resin to CT.
(4).High and low temperature is between -40~85℃,96hours . All parameters and electrical performance Not failed.

Package and Shipment
Good packing and careful handling required in order to guarantee the products under good condition. Avoid drop, shake and other destructive action during transport.

Storage
Air humidity is less than 95%(25℃) and any eroding gas or other harmful gas should be avoided.

www.sh-smarttechnology.com

Shanghai Smart Electronic Technology Co., Ltd. All Rights Reserved Copyright